Skip to main content

Over 150 LLM Providers · Over 5,300 Models The most extensible AI-powered pentesting platform. Open source. Star on GitHub

CVE-2021-22779

9.1 · CRITICAL
Published Jul 14, 2021 schneider-electric CWE-290 EPSS 1.02% (61th pctl)

Overview

CVE-2021-22779 is a critical-severity vulnerability affecting schneider-electric ecostruxure_control_expert. It was published on July 14, 2021 and has a CVSS 3.1 base score of 9.1 (CRITICAL).

This vulnerability has a CVSS 3.1 base score of 9.1, rated CRITICAL. It can be exploited remotely over the network. No authentication or special privileges are required for exploitation.

Technical Description

Authentication Bypass by Spoofing vulnerability exists in EcoStruxure Control Expert (all versions prior to V15.0 SP1, including all versions of Unity Pro), EcoStruxure Control Expert V15.0 SP1, EcoStruxure Process Expert (all versions, including all versions of EcoStruxure Hybrid DCS), SCADAPack RemoteConnect for x70 (all versions), Modicon M580 CPU (all versions - part numbers BMEP* and BMEH*), Modicon M340 CPU (all versions - part numbers BMXP34*), that could cause unauthorized access in read and write mode to the controller by spoofing the Modbus communication between the engineering software and the controller.

Remediation

Check the references section for vendor advisories and patches from schneider-electric. Update ecostruxure_control_expert to the latest patched version. If immediate patching is not possible, review the CVSS vector to understand the attack surface and apply compensating controls such as network segmentation or access restrictions.

Affected Products

Vendor Product Versions Status
schneider-electric ecostruxure_control_expert >= 0, < 15.0 Affected

Frequently Asked Questions

What is CVE-2021-22779?

CVE-2021-22779 is a critical-severity vulnerability affecting schneider-electric ecostruxure_control_expert. It was published on July 14, 2021 and has a CVSS 3.1 base score of 9.1 (CRITICAL).

How severe is CVE-2021-22779?

This vulnerability has a CVSS 3.1 base score of 9.1, rated CRITICAL. It can be exploited remotely over the network. No authentication or special privileges are required for exploitation.

How do I fix or remediate CVE-2021-22779?

Check the references section for vendor advisories and patches from schneider-electric. Update ecostruxure_control_expert to the latest patched version. If immediate patching is not possible, review the CVSS vector to understand the attack surface and apply compensating controls such as network segmentation or access restrictions.

How can CyberStrike help with CVE-2021-22779?

CyberStrike's AI-powered security agents can automatically detect CVE-2021-22779 across your infrastructure using autonomous pentesting, DAST scanning, and HackBrowser. The platform continuously monitors for known vulnerabilities and provides actionable remediation guidance prioritized by real-world exploitability.